One major cause of some confusion is what to call the extra capacity in the
system that has not been replaced by the added wind capacity, and which
would run in parallel with wind generation. Various terms have been used and
are still being applied to this retained capacity, such as ‘backup capacity’,
which has caused perplexity (Laughton, 2002; Royal Academy of Engineering,
2002), or ‘shadow capacity’ (E.ON Netz, 2004). Other terms include ‘compen-
sating capacity’ and ‘balancing capacity’. Even ‘spare capacity’ is used,
although this can be misleading because the capacity is not spare in the sense
of being redundant and will certainly need replacing when it reaches the end
of its life. Interpreting the meaning of ‘backup capacity’ in the literature or
debate, therefore, requires an understanding of the definition to be used.
For any given demand, new conventional thermal plant capacity added can
replace existing conventional plant capacity on a one-for-one basis; but obvi-
ously with a variable source such as wind, this equality relationship does not
hold. In the last case shown in Figure 1.13, for example, although 25,000MW
of wind capacity were added to the system, only 4500MW were retired and
20,500MW of conventional thermal plant were retained. These figures were
calculated from simulations and based on a probabilistic risk assessment; but,
as with all simulated results, they may or may not be valid.
Recent simulated power generation results for 25GW of wind generation
across Britain (Renewable Energy Foundation, 2006) have been based on
Renewable Obligation Certificate (ROC) data from the office of the electricity
industry regulator, Ofgem, and correlated with historic wind data
(Meteorological Office). The results indicate that over the period of 1995 to
2006, on average, wind power in January would have varied by 94 per cent of
installed capacity, with power swings of 70 per cent of capacity over 30 hours
being commonplace. On average, the minimum output would be only 3.7 per
cent. Of more significance here are the maximum changes of national output
of 99 per cent of capacity in 1998 and 1999, and the minimum outputs of 0.6
per cent of capacity in 1999 and 1 per cent of capacity in 2006. In such circum-
stances, what should be the level of conventional plant retained for power
backup purposes – 100 per cent of the wind capacity or less?
Suffice it to say that for all practical purposes, there is a need for conven-
tional backup capacity appropriate to the risks assumed regarding the
acceptability of loss of supply of either power or energy. If the risk of loss of
supply of power is captured, measured and effectively removed from further
consideration by the use of a probabilistic ‘capacity credit’, as described above,
whatever the practical shortcomings of such an analysis, then ‘backup capac-
ity’ can be associated entirely with matching the potential loss of supply of
energy. It is only in this latter connection that the requirements for backup
capacity are explored further here; thus, in this chapter ‘backup capacity’
means that capacity required to ensure annual energy requirements are met. A
similar restricted use of meaning is found elsewhere (UKERC, 2006)
Backup capacity and grid energy demand requirements
Conventional generation can be considered to provide two services: energy
22 Renewable Electricity and the Grid
3189 J&J Renew Electricity Grid 6/8/07 7:34 PM Page 22