
Pipework and oil traps 121
Parallel pipework
When compressors are installed in parallel and share common suction and
discharge lines, they are usually open-type units. Hermetic and semi-hermetic
units are not used in case of a motor failure. The high temperatures resulting
from the motor failure of one motor compressor can cause a chemical break-
down of the refrigerant and oil, resulting in the contamination of the whole
system.
However, two or more hermetic or semi-hermetic units can be used to
accommodate a common load. When this is required each compressor is
connected to an independent circuit within the evaporator and the condenser,
so that they function without the possibility of cross-contamination. A single
condenser is normally preferred for ease of control, but a separate condenser
may be used for each compressor.
Discharge lines
Discharge lines should be installed so that the horizontal section is pitched
downwards to join the common line. This will provide a free draining trap,
preventing oil drain back to the idle compressor.
When the condenser is located above the compressors, separate risers should
be used. Oil traps should be included at the base of each riser if the net lift
to the condenser is more than 2 m. If the riser height is less than 2 m the oil
traps may be omitted.
Figure 77 shows a basic pipework arrangement for discharge lines.
Discharge line equalizing
When individual condensers are installed, discharge lines must be equalized
before they enter the condensers to allow them to function as one (Figure 78).
The pressure drop within equalizing lines is critical. For example, assume a
pressure drop of 0.03 bar (0.5 psig) in the equalizer line. The pressure differen-
tial between an idle and an active condenser will cause condensed refrigerant
from the active condenser to back through the liquid line to the idle condenser
in an effort to equalize.
Crankcase equalizing
Obviously it is also necessary to prevent unequal oil distribution between the
crankcases of the compressors. This is achieved by connecting an equalizer
line to tappings provided (Figure 78).