
Ove Arup & Partners Consulting Engineers PC
Fire Safety in Theaters– A New Design Approach
Part I Assessment of Fire Safety Measures in Proscenium Theaters
F:\06 PROJECTS\CURRENT PROJECTS\076040-49 THEATER PROJECT
DTX\REPORT\076040-49_THEATRE_R_20090910.DOC
Page A6/55 Ove Arup & Partners Consulting Engineers PC
10 September 2009
8.1.2 Fire Scenario 2
This model simulated approximately 490 seconds of real or actual time. The fire reached a
heat release rate of approximately 11 MW. A pine involving a surface area of approximately
1190 ft² may generate such a fire size (i.e., 11 MW) [1].
8.1.2.1
Sprinkler Activation
The heat release rates at the estimated time of first sprinkler activation at ceiling level are
shown in Figure A9 as a function of RTI. A “quick” response sprinkler (i.e., RTI=50 (ms)
1/2
)
responded at the heat release rate of approximately 1200 kW. Figure A10 provides the
activation times of each sprinkler modeled (11 ft x 11 ft spacing). The cooling effects of
water spray were not included in the model.
0
500
1000
1500
2000
2500
0 50 100 150 200 250 30
RTI (m s)^0.5
HRR (kW)
Ceiling Sprinkler
Figure A9 – RTI vs. HRR at first sprinkler activation time in fire scenario 2 in the small-sized
theatre (activation temperature = 74°C , RTI=50 (ms)
1/2
and C- factor = 0.7 (m/s)
½
)
315s 284s 261s 237s 229s 212s
(4654 kW) (3783 kW) (3195 kW) (2635 kW) (2460 kW) (2108 kW)
343s 289s 269s 240s 214s 159s
(5518 kW) (3918 kW) (3394 kW) (2702 kW) (2148 kW) (1186 kW)
344s 281s 260s 242s 216s 210s
(5550 kW) (3704 kW) (3171 kW) (2747 kW) (2189 kW) (2069 kW)
Figure A10 – Ceiling sprinkler activation time and corresponding heat release rate in fire
scenario 1 in the small-sized theatre (activation temperature = 74 °C, RTI =50 (ms)
1/2
, and C-
factor = 0.7 (m/s)
½
)