
//INTEGRAS/KCG/P AGIN ATION/ WILEY /WPS /FINALS_1 4-12- 04/0470855088_ 13_CHA12 .3D – 268 – [257–282/26]
20.12.2004 7:43PM
12.3.5 Location of supplying VARs within a wind farm
There is a strong advantage in supplying VAR support for induction machines at or
near the induction machine, particularly considering the system topology of typical
wind farms. By providing it at the wind turbine the increased risk of ferro-resonance is
diminished, and harmonic problems and risks are less likely to arise. Also, effective use
can be made of wind turbine power system components, resulting in a lower-cost and
more easily maintained system.
In standard project design, each wind turbine sits behind its own transformer,
having significant impedance, typically 5 % to 6 %, and also behind the wind farm
substation transformer and collection system. Substation transformers typically
have 7 % to 8 % impedance, but since these have a far larger rating than any wind
turbine and may serve many wind turbines their impedance impact at the individual
turbine is relatively small. Some applications of VAR capacitors use dampening
inductance inserted with each bank of capacitors. These typically are in the order of
6 % to 7 % impedance. The available transformer impedance, coupled with careful
system design, can achieve low harmonic currents without the added cost and
complexity of the dampening inductors. Dampening inductors have generally not
been used on most wind farm capacitor installations in the USA and, where they
have been used, they have not dramatically diminished harmonic issues but do
reduce harmonic currents.
In Figure 12.4, the voltage impact of VAR support capacitors is shown for a variety
of locations for the VARs – at the wind turbine, on the wind farm collection system and
externally, on the high voltage (HV) grid, usually supplied by the utility.
Wind turbine case (a) in Figure 12.4 is of a typical Type A or B wind turbine with no-
load VAR support, what has typically been the standard product offering of most
manufacturers. In this configuration, and wi th a good, low VAR demand generator,
there will be about 1.8 % voltage drop at the wind turbine. This is solely attributable to
inadequate VARs causing a drop in generator voltage with increasing generation.
Wind turbine case (b) in Figure 12.4 has sufficient supplemental VARs at the wind
turbine to carry its share of the VARs need ed to provide a 0.95 power factor at the point
of interconnection. This causes a 3.7 % increase in generator voltage at the turbine. One
or two tap adjustments on the wind turbine transformer can accommodate that voltage
rise, and this will also cause the transformer to be less saturated – a desirable situation.
Lower saturation is also helpful with harmonics.
There are other significant issues that must also be addressed with respect to island-
ing, and one of the consequences of detail oversight is shown later, in Figure 12.7. In the
case illustrated, slow-acting medium-voltage vacuum breakers acted slowly and left
VAR support on an island for far too long. When the energy transfer stopped, this
resulted in a substantial overvoltage condition for a short period (see Section 12.3.9).
Interestingly, Figure 12.9 is of the same event, and at that facility the event was handled
without significant consequence (see Section 12.3.11). On the island, the excess VARs
caused the Type A or B induction machines to overexcite and climb to the maximum of
their saturation curve until the condition cleared.
Good protection and a reasonably rapid speed of response to such conditions is
important. Generally, 0.2 to 0.3 seconds is an adequate and effective time to clear
268 Wind Power on Weak Grids