
Operating principles and symptoms
39
3 The thermostatic expansion valve may be incorrectly adjusted or defec-
tive through partial loss of the phial charge, and therefore will not open
sufficiently. A total loss of the valve phial charge will result in a complete
blockage and a starved evaporator. Some expansion valves have replaceable
cartridges and screens. The cartridge is stamped with an orifice size; too
small an orifice can result in a starved evaporator.
4 Some plants employ evaporator defrost systems which incorporate a
magnetic valve or solenoid valve. This valve, installed in the liquid line,
will stop refrigerant flow to the evaporator when a defrost period is
initiated by a timing device. This enables the evaporator to be evacuated
of refrigerant so that, when the defrost heaters have completely cleared
the evaporator of frost, an excessive build-up of pressure will be prevented
during the period of continued application of heat.
Each of these conditions will result in lower than normal operating pressures.
When there is a shortage of refrigerant, pressures will be lower than normal.
However, the reduction in pressure may be so slight as not to be readily
detected, other than by a loss of evaporating capacity and the longer running
time of the unit. If the shortage is considerable, both suction and discharge
pressures will be very low; if the system temperature control consists of a
thermostat only, the unit will run continuously with poor refrigerating effect.
When a low pressure switch is in circuit, the compressor will short cycle (cut
in and out quickly) on this control.
Likewise, any restriction in the refrigerant supply will produce the same
symptoms on the low side of the system. It is possible for the compressor to
operate continuously on a deep vacuum if a low pressure switch is not used. A
complete blockage, preventing refrigerant from entering the evaporator, will
cause a low pressure switch to stop the compressor; it will not restart because
there will be insufficient pressure rise from the evaporator to actuate the
switch.
High suction and low discharge pressures
This condition is usually due to a fault within the compressor, such as broken
valve reeds or incorrect seating of the valve reeds.
If the suction reeds are at fault, some of the discharged vapour will be
forced back into the suction side of the compressor as the piston reaches the
top of its stroke.
Faulty discharge reeds will contribute to longer running time, poor
refrigeration effect and lower than normal operating head pressure. During
an off cycle the discharged vapour will leak back into the cylinder(s), causing