In summary, a brief description of regulations in the United States and
determination of CT values are presented. Under the SWTR, all surface
water supplies and groundwater supplies that are under the influence
of surface water must calculate CT values daily during peak hourly
flow. A minimum of 3-log Giardia lamblia and 4-log virus removal and/or
inactivation performance must be achieved at all times to comply with
the existing SWTR. The CT values are used to evaluate the achievement
of disinfection and to determine compliance with the SWTR. They also
are used to compute the log inactivation of Giardia and viruses during
water treatment and to construct a disinfection profile.
To calculate the CT value, operation data, e.g. disinfectant concen-
tration, water pH, and water temperature, should be measured daily
during the peak hourly flow. Contact time (T
10
), actual calculated CT
value (CT
cal
), 3-log Giardia inactivation (CT
99.9
from Table 5.7), and/or
4-log virus inactivation (from Table 5.9), CT
cal
/CT
99.9
, and CT
cal
/CT
99.99
should be calculated for the estimated segment log inactivations. The
total plant log inactivation is the sum of all segment log inactivations.
The daily log inactivation values can be used to develop a disinfection
profile for the treatment system.
18.5 Disinfection by-products
Water disinfection and its by-products. Chlorine has been widely used as
a disinfectant in water treatment process to kill or inactivate waterborne
pathogens. Chlorine disinfection of public drinking water had dramati-
cally reduced outbreaks of illness. In 1974, chloroform (trichloromethane)
was discovered as a disinfection by-product (DBP) resulting from the
interaction of chlorine with natural organic matter in water. This find-
ing raised a serious dilemma that water chlorination clearly reduced the
risk of infectious diseases and might also result in the formation of poten-
tially harmful DBP with this exposure in drinking water. DBP problem
is currently most concerned by water supply professionals.
Chlorine, chlorine dioxide, chloramines, ozone, and potassium per-
manganate are used in US water treatment plants as a disinfectant.
Table 5.11 lists some of the microorganisms targeted by disinfection
practice and some of more appropriate disinfectants for each microor-
ganism. Based on the types of disinfectants used, the numbers of water
supplies are roughly (keep changing) 22,000 (91.6%), 360 (1.5%), 140
(0.6%), 300 (1.3%), and 1200 (5.0%), respectively. The disinfectants are
often so powerful that they nonselectively react with other substances
in the water. There are actually thousands of DBPs. When natural
waters are disinfected, more than 100 potentially toxic halogenated
compounds can be created (Gray et al., 2001). The compounds of concern
are halogenated methanes, haloacetic acids, and nitrosamines.
Public Water Supply 491