
! 
_-  _, ,__ 
,.  .-  -~-  --~  -- 
be  used.  The  paper  can  be  obtained  at  most  office  supply  stores.  Two 
coordinates  are  shown  on  the  figure. 
The  vertical  coordinate  is  for  the 
flow  scales,  and  the  horizontal  is  for  the  exceedance  percentage.  The 
seven  USGS exceedance  values  are  indicated  below  the  horizontal  axis. 
The  vertical  axis  is  not  scaled  because  the  tt.  scales  that  will  be 
shown  depend  on  the  amount  of  flow  to  be  plotted.  The  easiest  method  to 
determine  the  vertical  scales  is  as  follows.  First,  make  the  axis  6  to 
8  inches  long  and  divide  it  into  convenient  increments.  For  example,  assume 
that  the  USGS  10%  exceedance  flow  is  390  cfs.  Wake  the  axis  8  inches  long, 
and  find  the  next  larger  number  above  390  into  which  8  will  divide  evenly. 
Eight  will  divide  into  400  fifty  times. 
Therefore,  make  the  increments 
50  cfs  per  inch.  Figure  3-14  is  a  flow  duration  curve  for  the  exceedance 
values  given  in  Table  3-3. 
Since  in  this  example  the  10%  exceedance  flow 
is  130  cfs,  the  vertical  axis  was  made  7  inches  long  and  a  20  cfs  per  inch 
increment  was  selected.  Look  at  Table  3-3  for  95%  exceedance;  the  flow  is 
8.1  cfs. 
To  plot  the  first  point,  place  one  straightedge  on  the  graph  so 
that  it  passes  vertically  through  the  95%  mark,  and  another  so  that  it 
passes  horizontally  through  the  8.1  cfs  flow  level;  mark  the  point  where 
the  two  straightedges  cross. 
You  can  use  a  draftsman's  right  triangle  for 
thi.s  purpose. 
Repeat  this  procedure  until  the  other  six  points  are  plotted. 
Connect  the  points  together  to  form  a  curve.  A  drafting  tool  called  a 
french  curve  will  aid  in  drawing  a  smooth  curve,  but  its  use  is  not 
necessary.  You  can  probably  obtain  satisfactory  results  by  connecting  each 
point  with  a  straight  line. 
The  flow  duration  curve  for  the  gage 
exceedance  is  now  plotted. 
Next,  the  scale  for  the  site  flow  needs  to  be  developed.  Refer  back 
to  the  previous  subsection  in  which  the  correlation  values  were  computed 
[last  column  of  the  flow  table  (Figure  3-5)].  Find  the  average  correlation 
value  by  adding  the  numbers  together  and  dividing  by  the  number  of  readings. 
C 
= 
Cl  +  c2  +  c3  +  . . .  cn 
n 
(3-11) 
3-44