
168
Electric Power Distribution Handbook
So, a single-phase 50-kVA transformer with a high-voltage winding of
12470GrdY/7200 V has a full-load current of 6.94 A on the primary. On a 240/
120-V secondary, the full-load current across the 240-V winding is 208.3 A.
Table 4.5 and Table 4.6 show the standard single-phase winding connec-
tions for primary and secondary windings. High-voltage bushings are
labeled H*, starting with H1 and then H2 and so forth. Similarly, the low-
voltage bushings are labeled X1, X2, X3, and so on.
The standard North American single-phase transformer connection is
shown in Figure 4.5. The standard secondary load service is a 120/240-V
three-wire service. This configuration has two secondary windings in series
with the midpoint grounded. The secondary terminals are labeled X1, X2,
and X3 where the voltage X1-X2 and X2-X3 are each 120 V. X1-X3 is 240 V.
Power and distribution transformers are assigned polarity dots according
to the terminal markings. Current entering H1 results in current leaving X1.
The voltage from H1 to H2 is in phase with the voltage from X1 to X3.
On overhead distribution transformers, the high-voltage terminal H1 is
always on the left (when looking into the low-voltage terminals; the termi-
nals are not marked). On the low-voltage side, the terminal locations are
different, depending on size. If X1 is on the right, it is referred to as
additive
polarity
(if X3 is on the right, it is
subtractive polarity
). Polarity is additive if
the voltages add when the two windings are connected in series around the
transformer (see Figure 4.6). Industry standards specify the polarity of a
TABLE 4.5
Winding Designations for Single-Phase Primary and Secondary Transformer
Windings with One Winding
Nomenclature Examples Description
E 13800 E shall indicate a winding of E volts that is suitable for
D
connection on an E volt system.
E/E
1
Y 2400/4160Y E/E
1
Y shall indicate a winding of E volts that is suitable
for
D
connection on an E volt system or for Y connection
on an E
1
volt system.
E/E
1
GrdY 7200/12470GrdY E/E
1
GrdY shall indicate a winding of E volts having
reduced insulation that is suitable for
D
connection on
an E volt system or Y connection on an E
1
volt system,
transformer, neutral effectively grounded.
E
1
GrdY/E 12470GrdY/7200
480GrdY/277
E
1
GrdY/E shall indicate a winding of E volts with
reduced insulation at the neutral end. The neutral end
may be connected directly to the tank for Y or for single-
phase operation on an E
1
volt system, provided the
neutral end of the winding is effectively grounded.
E
1
= E
Note
:E is line-to-neutral voltage of a Y winding, or line-to-line voltage of a
D
winding.
Source
: IEEE Std. C57.12.00-2000. Copyright 2000 IEEE. All rights reserved.
3
1791_C04.fm Page 168 Thursday, August 7, 2003 11:18 AM
(C) 2004 by CRC Press LLC