
Faults 323
() in one of the phases (see Figure 7.9). To make sure a primary fuse
coordinates with a secondary device, shift the minimum-melting time-cur-
rent curve of the primary-side fuse to the left by a factor of 0.866 =
(after also adjusting for the transformer turns ratio). The current differences
also mean that the transformer is not protected as well for single-phase faults;
a primary-side fuse takes longer to clear the single-phase fault since it sees
less current than for a three-phase or line-to-line fault.
Fault currents are only different for unbalanced secondary currents. For a
three-phase secondary fault, the per-unit currents on the primary equal those
on the secondary (with the actual currents related by the turns ratio of the
transformer). A wye – wye transformer does not disturb the current rela-
tionships; the per-unit currents on both sides of the transformer are equal.
In a floating wye – delta, similar current relationships exist; a line-to-line
secondary fault shows up on the primary side on all three phases, one of
which is 1.15 per unit (see Figure 7.10). For a floating wye – delta transformer
with a larger center-tapped lighting leg and two power legs, fault current
calculations are difficult. Faults can occur from phase to phase and from
phase to the secondary neutral, and the lighting transformer will have a
different impedance than the power leg transformers. For an approach to
modeling this, see Kersting and Phillips (1996).
7.2.2 Fault Profiles
Fault profiles show fault current with distance along a circuit. Determining
where thermal or mechanical short-circuit limits on equipment may be
exceeded, helping select or check interrupting capabilities of protective
equipment, and coordinating protective devices are important uses of fault
profiles. Figure 7.11 and Figure 7.12 show typical fault current profiles of
distribution circuits.
Some general trends that the fault profiles show are:
• Distance — The fault current drops off as the inverse of distance (1/d).
• Ground faults — On overhead circuits, the ground fault current
falls off faster (and the ground fault current is generally lower)
FIGURE 7.10
Per-unit fault-currents on both sides of a wye – delta transformer.
1/3
1
1.15
0.577
1/3
2/3
0.577
23
32
1791_book.fm Page 323 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC