
326 Electric Power Distribution Handbook
than the three-phase fault current. The zero-sequence reactance is
generally over three times the positive-sequence reactance, and the
zero-sequence resistance is also higher than the positive-sequence
resistance.
• System voltage — On higher-voltage distribution systems, the fault
current drops off more slowly. The actual line impedance does not
change with voltage (Z
S
ª1 W/mi), and since I = V
LN
/Z, it takes more
impedance (more circuit length) to reduce the fault current.
• Cables — Underground cables have much lower reactance than over-
head circuits, so the fault current does not fall off as fast on under-
ground circuits. Also, note that X/R ratios are lower on cables.
• Profiles — The three-phase and ground-fault profiles of underground
cables are similar. The zero-sequence reactance can actually be
smaller than the positive-sequence reactance (but the zero-sequence
resistance is larger than the positive-sequence resistance).
7.2.3 Effect of X/R Ratio
In a reactive circuit (high X/R ratio), it is naturally more difficult for a
protective device such as a circuit breaker to clear a fault. Protective devices
clear a fault at a current zero. Within the interruptor, dielectric strength builds
up to prevent the arc from reigniting after the current zero. In a resistive
circuit (low X/R ratio), the voltage and current are in phase, so after a current
zero, a quarter cycle passes before the voltage across the protective device
(called the recovery voltage) reaches its peak. In a reactive circuit, the fault
current naturally lags the voltage by 90∞; the voltage peaks at a current
zero. Therefore, the recovery voltage across the protective device rises to its
peak in much less than a quarter cycle (possibly in 1/20th of a cycle or less),
and the fault arc is much more likely to reignite.
Another factor that makes it more difficult for protective devices to clear
faults is asymmetry. Circuits with inductance resist a change in current. A
short circuit creates a significant change in current, possibly creating an
offset. If the fault occurs when the current would naturally be at its negative
peak, the current starts at that point on the waveshape but is offset by 1.0
per unit. The dc offset decays, depending on the X/R ratio. The offset is
described by the following equation:
where
i(t) = instantaneous value of current at time t
it I ft I e
rms rms
ft
XR
() sin( ) sin( )
/
=+---
-
22 2
2
pbq bq
p
ac component
decaying dc component
12444434444 1 2444434444
1791_book.fm Page 326 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC