
3 SOLAR COLLECTOR TECHNOLOGIES AND SYSTEMS
879
with a collector area about 15 m
2
(see the top black circle
on the vertical red line, Figure 3). The same solar fraction
can be produced if the system is tilted 45º or 60º with 11 m
2
collector area.
Using the ET system, the same solar fraction can be
attained at a much reduced solar collector area at different
collector slopes.
In Fig. 4, the system with a 450 L tank, a solar fraction of
70% can be attained by the FP system tilted at 25º with a
collector area of nearly 18 m
2
; or, if tilted at 45 or 60º, the
same fraction can be attained with 12 m
2
collector area.
Using the ET system, the same solar fraction can be
attained with a collector area of about 8 – 9 m
2
at collector
slopes of 25 – 60º.
In Fig. 5, the system with a 630 L tank, a solar fraction of
75% can be attained by the FP system tilted at 25º with a
collector area of about 21 m
2
. If tilted at 45 or 60º, the same
fraction can be attained with a collector area of about 15 m
2
.
Using the ET system, the same solar fraction can be
attained with a collector area of about 9 – 11 m
2
at collector
slopes of 25 – 60ºC.
Effect of tank volume
From Figures 3 - 5 we can also see the effect of tank
volume on the performance of a system with a given
specification. For example, the points marked with a cross
star represent the FP system with a collector area of 14 m
2
tilted at either 45 or 60º. As shown, an increase in tank
volume from 315 L to 630 L increases the solar fraction
from about 67.5% to about 74%. However at higher tank
volumes (630 – 945) this effect is marginal (the results for
tank volumes above 630 are not shown).
Effect of Collector Slope
Four collector slopes were simulated to see how it affects
the systems’ performance. The 25º slope represents the
conventional roof pitch in South Australia, the 45º and 60º
represent the favourable slope angle in terms of solar gain
during winter. The 90º slope (vertical position) makes it
possible to position the solar system in the north wall of the
building.
As shown, for the FP system, 45º and 60º slopes give the
best solar fractions for fixed solar collector areas and tank
volumes. For the ET system, the 45º slope gives the highest
solar fraction for a fixed collector area and tank volume.
For both systems, the vertical position (90º) should be
avoided as it results in poor solar fractions.
Monthly System Performance
Figure 6 shows the monthly solar fraction of a system with
12 m
2
collector area mounted with 45º slope facing north
with a 450 L tank. The figure represents the trend of the
system’s thermal performance on a monthly basis in
general for both FP and ET systems.
As shown, the systems are able to provide most of the heat
energy requirements during summer, spring and autumn
and about 50% (FP) and 60% (ET) of the heating energy
requirements during the peak winter months of June –
August. The latter is mainly for winter space heating load.
The figure also shows a slightly better performance of the
ET system during the winter months compared with the FP
system.
0.0
0.2
0.4
0.6
0.8
1.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Month
Annual Solar Fraction
Fig. 6: Monthly Solar Fraction for A
C
= 12 m
2
, tank = 450
L, Slope = 45º.
It is worth comparing the results from the present study
with that from Europe. According to Charron et al. (2007),
small systems in the Netherlands consists of 4 to 6 m
2
collector with 0.3 m
3
storage tank. In Switzerland, Austria
and Sweden larger systems (with a solar fraction of 20 to
60%) typically use 15 – 30 m
2
of collector area with 1 – 3
m
3
thermal storage tank. The more favorable climatic
conditions for Australia make it possible to have smaller
systems with similar outputs.