
Electromagnetic compatibility (EMC)  127 
The voltage at the PCC will be distorted to an extent depending on the magnitude of the 
distorted current, the magnitude of the impedances and the ratio between them. The 
source impedance can easily be calculated from the system fault level and this is 
commonly used as the criteria for the permissible size of converter load. A high fault 
level means a low source impedance and vice versa. If the source impedance is low, then 
the voltage distortion will be low. The distribution impedance must be calculated from 
the design details of the distribution system. 
A high distribution impedance will tend to reduce the voltage at the point of common 
coupling but increase it at the converter connection terminals. This voltage distortion can 
cause interference with the electronic trigger circuits of the converter and give rise to 
other problems if it becomes too high. 
If the magnitude and the frequency of each harmonic current is known, a simple 
application of Ohm’s law will give the magnitude of each harmonic voltage and the sum 
of them will give the total distorted voltage. 
From AS 2279-1991 Part 2, the total harmonic distortion (THD) of voltage and current 
are given by the following formulae. Generally, it is sufficient to use values of n up to 25. 
 
 
%
100
2
n
2
1
T
   
V
  
V
  =  
V
=n
=n
Σ
∞
 
 
%
100
2
n2
1
T
   
I
  
I
  =  
I
=n
=n
Σ
∞
 
 
where:  V
T
 = Total harmonic voltage distortion 
I
T
 = Total harmonic current distortion 
V
1
 = Fundamental voltage at 50 Hz 
I
1
 = Fundamental current at 50 Hz 
V
n
 = nth harmonic voltage 
I
n
 = nth harmonic current 
 
The acceptable levels of harmonics in industrial power supply networks are clearly 
defined in Table 1 of the Australian standard AS 2279-1991 Part 2: disturbances in mains 
supply networks. Briefly, limits are set for the level of total harmonic voltage distortion, 
which are acceptable at the point of common coupling (PCC). The application of these 
standards requires the prior calculation of harmonic distortion at all points in the system 
before the converter equipment can be connected and, under certain circumstances, actual 
measurements of harmonic voltage to confirm the level of distortion. 
4.3.5  Methods of reducing harmonic voltages in the power supply 
The use of converters has many technical and economic advantages that will ensure their 
continued use in industrial and mining plants for many years ahead. In spite of the 
increase of harmonic distortion in power systems, their advantages far outweigh their 
disadvantages and their use will continue to grow. 
As outlined above, harmonic voltage distortion at the point of common coupling is the 
result of the flow of harmonic currents through the source impedance. On a stiff power 
system, where the source impedance is low, the voltage distortion will be low. However, 
the fault level will be high and the short circuit protection equipment will have to be rated 
accordingly. On a smaller power system, where the source impedance is high, the voltage 
distortion will tend to be higher.