
236 Practical Variable Speed Drives and Power Electronics
Insulation class Rated temp Alarm temp Trip temp
Class B
Class F
Class H
120
U
C
140
U
C
165
U
C
120
U
C
140
U
C
165
U
C
130
U
C
150
U
C
175
U
C
Figure A.2:
Typical temperature level settings used on rotating electrical machines
Due to the relatively slow transfer of heat to the sensors through the insulation medium,
PTC thermistors do not provide sufficiently fast protection for short circuits in motors or
transformers. Also, since they are usually located in the stator windings, they do not
provide adequate protection for rotor critical motors or for high inertia starting or stalled
rotor conditions. In these cases, to achieve complete protection, it is recommended that
PTC thermistors should be used in combination with electronic motor protection relays,
which monitor the primary current drawn by the motor.
The application of PTC thermistors as temperature sensors is only effective when:
• The rated response temperature (RRT) of the thermistor is correctly selected
for the class of insulation used on the winding.
• The thermistors are correctly located close to the thermally critical areas.
• There is a low thermal resistance between the winding and the PTC
thermistor. This depends on the electrical insulation between the winding and
the thermistor. Since thermistors need to be isolated from high voltages, it is
more difficult to achieve a low heat transfer resistance in HV motors, which
have greater insulation thickness.
Several thermistor sensors may be connected in series in a single sensor circuit,
provided that the total resistance at ambient temperatures does not exceed 1.5 kΩ. In
practice, and as recommended by IEC, up to six thermistor sensors can be connected in
series.
For a 3-phase AC motor, two thermistor sensors are usually provided in each of the 3
windings and connected in two series groups of three. One group can be used for alarm
and the other group for tripping of the motor. The alarm group is usually selected with a
lower rated response temperature (RRT); typically 5
o
C or 10
o
C lower than the tripping
group. If the operator takes no action, the tripping group is used to trip the motor directly
to prevent damage to the winding insulation. In many cases, users choose both groups to
have the same RRT. In this case, only one group of thermistors is used (one in each
phase) and these are then used for tripping the motor. This provides for one spare
thermistor in each phase.
The physical location of the thermistor sensors in an AC motor depends on the
construction of the motor, whether it has a cylindrical rotor or salient pole rotor, and
several other design and manufacturing variables. In some cases, the optimum location
may have to be determined from test experience.
Thermistor protection relays (TPR) are designed for mounting inside a control cubicle
or motor control center, usually on standard terminal rails. The Figure A.3 shows a
typical connection of two thermistor protection relays, and their associated groups of
thermistor sensors.
For alarm and trip control of a 3-phase AC induction motor. The performance of
thermistor protection relays can be affected by external electrical interference, where