
220 Electric Power Distribution Handbook
• Arrester currents were always less than 2 A.
• Under-oil arresters, which have superior thermal characteristics,
reached thermal stability and did not fail.
• Porcelain-housed arresters showed slow heating — sometimes
enough to fail, sometimes not, depending on the transformer type,
cable lengths, and arrester type. Elbow arresters showed slow heat-
ing — slower than the riser-pole arresters. Failure times for either
type were typically longer than 30 min.
With normal switching times of less than one minute, arresters do not have
enough time to heat and fail. Crews should be able to safely switch trans-
formers under most circumstances. Load — even 5% of the transformer
rating — prevents ferroresonance in most cases. The most danger is with
unloaded transformers. If an arrester fails, the failure may not operate the
disconnect, which can lead to a dangerous scenario. When a line worker
recloses the switch, the stiff power-frequency source will fail the arrester.
The disconnect should operate and draw an arc. On occasion, the arrester
may violently shatter.
One option to limit the exposure of the arresters is to put the arresters
upstream of the switch. At a cable riser pole this is very difficult to do without
seriously compromising the lead length of the arrester.
4.10.3 Switching Floating Wye – Delta Banks
Floating wye – delta banks present special concerns. As well as being prone
to ferroresonance, single-pole switching can cause overvoltages due to a
neutral shift. On a floating wye – delta, the secondary delta connection fixes
the transformer’s primary neutral close to ground potential. After one phase
of the primary wye is opened, the neutral can float far from ground. This
causes overvoltages, both on the secondary side and the primary side. The
severity depends on the balance of the load.
When crews open one of the power-leg phases, if there is no three-phase
load and only the single-phase load on the lighting leg of the transformer,
the open primary voltage V
open
reaches 2.65 times normal as shown in Figure
4.29. The voltage across the open switch also sees high voltage. The voltage
from B to B¢ in Figure 4.29 can reach over 2.75 per unit. Secondary line-to-
line voltages on the power legs can reach 1.73 per unit. The secondary delta
forces the sum of the three primary line-to-neutral voltages to be equal. With
single-phase load on phase C and no other load, the neutral shifts to the C-
phase voltage. The delta winding forces V
B¢N
to be equal to –V
AN
, which
significantly shifting the potential of point B¢.
The line-to-ground voltage on the primary-side of the transformer on the
open phase is a function of the load unbalance on the secondary. Given the
ratio of the single-phase load to the three-phase load, this voltage is [assum-
1791_C04.fm Page 220 Thursday, August 7, 2003 11:18 AM
(C) 2004 by CRC Press LLC