Mass transfer coefficient are influenced by total dissolved solids in the
liquid. Therefore, a correction factor ␣ is applied for wastewater
(Tchobanoglous and Schroeder, 1985):
(5.27)
Value of ␣ range from 0.3 to 1.2. Typical values for diffused and mechan-
ical aeration equipment are in the range of 0.4 to 0.8 and 0.6 to 1.2.
The third correction factor () for oxygen solubility is due to particu-
late, salt, and surface active substances in water (Doyle and Boyle, 1986):
(5.28)
Values of  range from 0.7 to 0.98, with 0.95 commonly used for waste-
water.
Combining all three correction factors, we obtain (Tchobanoglous and
Schroeder 1985)
(5.29)
where AOTR ⫽ actual oxygen transfer rate under field operating
conditions in a respiring system, kg ⋅ O
2
/kW ⋅ h
SOTR ⫽ standard oxygen transfer rate under test conditions at
20ºC and zero dissolved oxygen,
kg ⋅ O
2
/kW ⋅ h
␣, , ⫽ defined previously
C
s
⫽ oxygen saturation concentration for tap water at field
operating conditions, g/m
3
C
w
⫽ operating oxygen concentration in wastewater, g/m
3
C
s20
⫽ oxygen saturation concentration for tap water at
20ºC, g/m
3
Example 2: Aeration tests are conducted with tap water and wastewater at
16ºC in the same container. The results of the tests are listed below. Assume
the saturation DO concentrations (C
s
) for tap water and wastewater are the
same. Determine the values of K
L
a for tap water and wastewater and a values
at 20ºC.
Assume ⫽ 1.024
solution:
Step 1. Find DO saturation concentration at 16ºC
From Table 1.2
C
s
⫽ 9.82 mg/L
AOTR 5 SOTRsadsbdsu
T220
da
C
s
2 C
w
C
s20
b
b 5
C *swastewaterd
C *stap waterd
a 5
K
L
a swastewaterd
K
L
a stap waterd
Public Water Supply 353