180  Practical Variable Speed Drives and Power Electronics   
 
 
The correct procedure is: 
• The first step is to select a correctly rated electric motor 
• Only when this is completed, a suitable AC converter is chosen to match the 
requirements of the motor 
 
From the motor point of view, the main factors which need to be considered are the 
motor power rating (kW), the number of poles (speed) and the frame size so that the load 
torque on the motor shaft remains within the continuous torque capability of the motor at 
all speeds within the speed range. High torques of short duration, such as starting torque, 
can usually be easily accommodated within certain limits outlined below. 
 :NKRUGJGHOROZ_ULIUT\KXZKXLKJYW[OXXKRIGMKSUZUXY
When selecting an AC motor for any drive application, the most important requirement is 
to ensure that the motor does not become overloaded or stall under all circumstances of 
speed and load, i.e. over the entire speed range. 
To stay within the temperature rise limits of the motor, the torque required by the load 
for starting, acceleration and for continuous running must be within the rated output 
torque capacity of the motor. 
For AC motors connected to the power supply direct-on-line (DOL), it is usually 
sufficient to ensure that load torque is sufficiently below motor torque at the rated speed 
of the motor, for example the torque at 1450 rev/m on a 4 pole motor. These fixed speed 
drives operate only at one speed. It may also be necessary to ensure that the starting 
torque of the motor is higher than the breakaway torque of the load. 
In the case of a variable speed drive, the load torque usually changes with speed, so it is 
essential to check that the motor torque exceeds the load torque at all speeds in the speed 
range. For example, a centrifugal pump has a variable torque characteristic, where the 
starting torque is low and the torque increases as the square of the speed as shown in 
Figure 7.6. Other loads, such as a conveyor, may have a constant torque characteristic, 
where the load torque remains constant for all speeds, as shown in Figure 7.7. 
The continuous load torque capacity (loadability) of a standard TEFC squirrel cage 
induction motor used with VVVF converters is always lower than the rated torque of the 
motor itself for the following reasons: 
• At all speeds, the load capacity is reduced as a result of additional heating in 
the motor caused by harmonic currents, however small. These occur because 
the output current waveform of the converter is not completely sinusoidal, 
even with modern PWM inverters with switching frequencies around 10 kHz. 
 
Traditionally, a de-rating of between 5% and 10% was used, depending on the 
type of motor (number of poles) and the type of converter. But, it has become 
common practice with modern PWM inverters to make provision for no de-
rating at all. This relies on the fact that modern IEC motors always have a 
built-in thermal reserve (refer to Chapter 2), which will accommodate any 
additional heating. Also, the mechanical load is seldom exactly equal to the 
motor rating and is often lower by as much as 20%. 
It is considered good engineering practice to allow a small margin of safety, 
so a de-rating of up to 5% is usually provided.