
UNIT 43 Heat-Pump Controls 389
DEFROST TIMER
When the heat pump is used in the heating mode of
operation, it removes heat from the air and delivers
it inside the living area. This means that the outside
heat exchanger is being used as the evaporator and
cold refrigerant is circulated through it. Any mois-
ture in the air can cause frost to form on the coil
and reduce the air ow through it. This will reduce
the ef ciency of the unit. For this reason, it is gener-
ally necessary to defrost the outside heat exchanger.
Defrosting is done by disconnecting the condenser
or outside fan motor and reversing the ow of
refrigerant through the coil. This causes the unit to
temporarily become an air conditioner and warm
refrigerant is circulated through the coil.
Before the defrost cycle can be activated,
two separate control conditions must exist. The
defrost thermostat, located on the outside heat
exchanger, must be closed; and the defrost timer
must permit the defrost cycle to begin. A schematic
diagram of a basic defrost control circuit is shown
in Figure 43–2. Notice that the defrost timer is con-
nected in parallel with the compressor. This means
that the timer can operate only when the compres-
sor is in operation. Notice also that the defrost cycle
energizes the
reversing valve solenoid. This
means that this unit is in the heating mode when
the solenoid is deenergized.
Notice the defrost timer contains two contacts,
DT1 and DT2. DT1 is normally open and DT2 is
normally closed. The defrost relay (DFR) contains
three contacts. DFR1 is normally closed and is con-
nected in series with the outside fan motor. DFR2
is normally open and is connected in parallel with
contact DT1. Contact DFR3 is normally open and is
connected to the reversing valve solenoid.
The schematic shown in Figure 43–3 illustrates
the condition of the circuit when the defrost cycle
rst begins. Notice that the defrost timer (DT) has
caused contact DT1 to close, but contact DT2 has
not opened. The contacts of the defrost timer are
operated by two separate cams. The cams are so
arranged that contact DT1 will close before DT2
opens.
The schematic in Figure 43–4 illustrates the
condition of the circuit immediately after the defrost
relay has energized. Notice that all DFR contacts
TWO-STAGE THERMOSTATS
The two-stage thermostat is a thermostat that con-
tains two separate mercury contacts. It is similar to
the programmable thermostat except that the two
mercury contacts cannot be set independently of
each other. The mercury contacts of the two-stage
thermostat are so arranged that one contact will
make connection slightly ahead of the other. For
example, assume the heat pump is being used in the
heating mode. Now assume that the temperature
drops. One of the contacts will make connection
rst. This contact turns on the compressor and heat
is provided to the living area. If the compressor can
provide enough heat to raise the temperature to the
desired level, the second mercury contact does not
make connection. If the compressor cannot provide
the heat needed, the second mercury contact will
close and turn on the electric-resistance heating ele-
ments to provide extra heat to the living area.
THE SEQUENCE TIMER
The sequence timer is an on-delay timer used
to connect the heating elements to the line in stages
instead of all at once. Most sequence timers contain
two or three contacts and are operated by a small
heating element that heats a bimetal strip. When the
bimetal strip becomes hot enough, it snaps from one
position to another and closes the two contacts. A pho-
tograph of this type of timer is shown in Figure 43–1.
Figure 43–1
Sequence relay. (Courtesy of Emerson Electric Co., White-Rodgers Division).