
UNIT 40 Introduction to Troubleshooting 365
THE HOPSCOTCH METHOD
A very common troubleshooting method is called
the hopscotch method. As the name implies,
you jump from one component to another until the
open part of the circuit is found. In the example in
Figure 40–10, the voltmeter is connected across the
coil of contactor CC. To use the hopscotch method
of troubleshooting, leave one voltmeter probe con-
nected to one side of the transformer and connect
the other probe on the other side of the next compo-
nent in line, Figure 40–11. If the voltmeter indicates
24 volts, it means that the ow switch is open and
preventing the compressor contractor from energiz-
ing. If the voltmeter indicates 0 volts, it means that
there is still an open condition somewhere else in
the circuit that is preventing the voltmeter from
receiving a ow or current. The 0 volt reading does
not mean that contact FL is closed. Contact FL could
be open but there is something else open in the cir-
cuit ahead of it. In this example, it will be assumed
that the voltmeter indicates 0 volt.
The next step is to hopscotch to the next
component, which is the low pressure switch,
Figure 40–12. If the voltmeter indicates a voltage
of 24 volts, it is an indication that the low pressure
switch is open. If the voltmeter indicates 0 volts,
the voltmeter probe should be moved across the
next component in line. For this example it will be
assumed that the voltmeter indicates a voltage of
24 volts. The next step is to determine if the switch is
defective or if the system is low on refrigerant.
THE OHMMETER
The ohmmeter is generally used in two primary
ways:
1. To measure the amount of resistance in a
circuit.
2. To test a circuit for continuity.
Assume that a service technician is sent on a ser-
vice call. The only information given is that the
air conditioner will not run. Using the same circuit
in the previous example, assume that the techni-
cian places a jumper across the thermostat and
discovers that the condenser fan operates but the
Figure 40–9
Fused jumper for shorting control components.
(Source: Delmar/Cengage Learning)
is recommended, Figure 40–9. The jumper contains
a small amp value fuse such as 3 or 4 amperes. If
the jumper should be accidentally connected across
power, the fuse will blow instantly. Assume then
that the thermostat was jumped; the fan motor
started but the compressor did not.
The next step is to determine what could be the
problem. Looking at the schematic, make mental notes
of what could cause the compressor not to start.
1. CC contactor is defective.
2. Flow switch FL did not close.
3. The low-pressure switch, LP, is open.
4. The high-pressure switch, HP is open.
5. CC load contacts are burned out and not con-
necting power to the compressor.
6. The compressor overload is open.
7. The compressor start capacitor is bad.
8. The compressor motor is bad.
The next logical step is probably to determine if
voltage is being applied to the coil of the compressor
contactor. This can be done by jumping the thermo-
stat and checking across CC coil with a voltmeter,
Figure 40–10.
For this example, it will be assumed that the volt-
meter indicated that there was no voltage applied to
contactor coil CC.