
Heat Pumps 301
3
Inside coil
7
8
6
Vapor
Compressor
1
2
3
Outside coil
4
6
Compressed vapor
Liquid refrigerant
5
Figure 6.8 A vapor-compression heat pump running for heating (Courtesy of D&H Climate Control).
accomplished by reversing the flow of refrigerant through a device found in heat pumps knows as
a “reversing valve”. This valve is automatically controlled through the thermostat when switched
to heat.
Figure 6.8 shows the heat pump in the heating mode of operation (e.g., in winter the heat
exchanger located outside the house functions as an evaporator, absorbing low-temperature heat
from the environment). Switching the heat pump from the cooling mode to the heating mode
is achieved simply by switching the direction of the refrigerant flow. The difference between
Figures 6.7 and 6.8 is that the reversing valve (2) directs the compressed refrigerant to the inside
coil first. This makes the inside coil the condenser and releases the heat energy (3-4). This heated
air is ducted to the home. The outside coil is used to collect the heat energy (3-7). This now
becomes the evaporator. Both heating and A/C modes do exactly the same thing. They pump
heat from one location to another. In these examples, the heat in the air is moved out of or into
the home.
There is usable heat in outdoor air at temperatures as low as −8.5
◦
C. As the temperature of the
outdoor air decreases, however, the heating capacity of the heat pump diminishes proportionately,
resulting in lower discharge air temperatures at the air registers and gradual cooling of the house.
To supplement the heating capacity of the heat pump, electric resistance heating elements are used,
which automatically engage via the thermostat when this condition occurs.
6.10.3 Single-Stage Vapor-Compression Heat Pump with Subcooler
A simple modification can be made to the four-component cycle to make it, in some situa-
tions, considerably more efficient. This is the addition of a refrigerant subcooler, as shown in
Figure 6.9a. This extra heat exchanger extracts heat from the hot liquid refrigerant before it
goes through the expansion valve. This leads to less flash gas formation through the expansion
valve. Hence, the same compressor is doing more useful cooling and heating, with no extra power
consumption (note that the compressor is “unaware” of whether its suction vapors are formed
across the expansion valve or through boiling in the evaporator). Figure 6.9b shows the effect
of subcooling on a Mollier chart. In both cases illustrated, the primary heating is carried out
between 70 and 75
◦
C. In the case of a subcooler the hot refrigerant (80
◦
Cwhenleavingthe
condenser) is cooled to 30
◦
C by a stream of air. This extra free heat can successfully be used
by integrating an air space heating unit with the main hot water system. The financial advantage
is considerable.