
Short-Circuit Protection 405
really possible if the transformer is used for its most economic performance
(which means overloading a transformer at peak periods). To avoid nuisance
fuse operations from load, we must use a fuse big enough so that thermal
overload protection is impossible. It is also argued that most transformer
failures start as failures between turns or layers and that a smaller, faster
fuse detects this more quickly. Tests have indicated that a smaller fuse might
not be much better than a larger fuse at detecting interwinding failures
(Lunsford and Tobin, 1997) (pressure-relief valves limit tank pressures very
well during this type of failure). All together, the arguments for a smaller
fuse are not enough to overcome the concerns with nuisance fuse operations.
If overload protection must be used, use a surge resistant fuse (it has a slower
characteristic for high-magnitude, short-duration currents).
A few utilities practice group fusing where a lateral fuse provides protec-
tion to all of the transformers on the tap. If the transformer failure rate
(including bushing faults) is low enough, then this practice will not degrade
the overall frequency of interruptions significantly. One of the major disad-
vantages of this approach is that an internal transformer failure on a tap
may be very hard to find. This drives up repair time (so the duration reli-
ability numbers suffer but not necessarily the frequency indices). Also, the
beneficial feature of being able to switch the transformer with the fused
cutout is lost if group fusing is used.
Widely used, completely self-protected transformers (CSPs) have an inter-
nal weak-link fuse; an external fuse is not needed (although they may need
an external current-limiting fuse to supplement the weak link).
Transformer bushing faults often caused by animals can have different
impacts depending on fusing practices. A fault across a primary bushing
operates an external transformer fuse. If the transformer is a CSP or group
fusing is used, the upstream tap fuse operates (so more customers are
affected).
Current-limiting fuses are regularly used on transformers in high fault-
current areas to provide protection against violent transformer failure.
NEMA established tests which were later adopted by ANSI (ANSI C57.12.20-
1988) for distribution transformers to be able to withstand internal arcs.
Transformers with external fuses are subjected to a test where an internal
arcing fault with an arc length of 1 in. (2.54 cm) is maintained for 1/2 to 1
cycle. It was thought that 1 in. (2.54 cm) was representative of the length
that arcs could typically achieve. The current is 8000 A. Under this fault
condition, the transformer must not rupture or expel excessive oil. Note that
this test does not include all of the possible failure modes and is no guarantee
that a transformer will not fail with lower current. For example, a failure
with an arc longer than 1 in. has more energy and ruptures the transformer
at a lower level of current.
Table 8.7 shows rupture limits for several types of transformers based on
tests for the Canadian Electrical Association. If fault current values exceed
those given in this table, consider using current-limiting fuses to reduce the
chance of violent failures (the CEA report considers the limits provisional
1791_book.fm Page 405 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC