
Short-Circuit Protection 417
a downstream line recloser. Consider a station recloser R1 and a downstream
line recloser R2 each with one fast curve (A) and two delayed curves (B). If
a permanent fault occurs downstream of R2, R2 will first operate on its A
curve. If the fast curves of R1 and R2 are coordinated, R1 will not operate.
After a delay, R2 recloses. The fault is still there, so R2 operates on its delayed
curve (its B curve). Now, R1 does operate because it is on its A curve which
operates before R2’s B curve. After R1 recloses, R2 should then clear the
fault on its B curve, which should operate before R1’s B curve. The fault is
still cleared properly, but customers upstream of R2 have extra momentary
interruptions.
A more advanced form of coordination called sequence coordination removes
this problem. Sequence coordination is available on electronic reclosers and
also on digital relays controlling circuit breakers. With sequence coordina-
tion, the station device detects and counts faults — but does not open — for
a fault cleared by a downstream protector on the fast trip. If the fault current
occurs again (usually because the fault is permanent), the station device
switches to the time-overcurrent element because it counted the first as an
operation. Using this form of coordination eliminates the momentary inter-
ruption for the entire feeder for permanent faults downstream of a feeder
recloser. On a relay or recloser that has sequence coordination, if the device
senses current above some minimum trip setting and the current does not
last long enough to trip based on the device’s fast curve, the device advances
its control-sequence counter as if the unit had operated on its fast curve. So
when the downstream device moves to its delayed curve, the upstream
device with sequence coordination also is operating on its delayed curve.
With sequence coordination, for the fast curves, the response curve of the
upstream device must still be slower than the clearing curve of the down-
stream device.
8.7 Fuse Saving vs. Fuse Blowing
Fuse saving is a protection scheme where a circuit breaker or recloser is used
to operate before a lateral tap fuse. A fuse does not have reclosing capability;
a circuit breaker (or recloser) does. Fuse saving is usually implemented with
an instantaneous relay on a breaker (or the fast curve on a recloser). The
instantaneous trip is disabled after the first fault, so after the breaker recloses,
if the fault is still there, the system is time coordinated, so the fuse blows.
Because most faults are temporary, fuse saving prevents a number of lateral
fuse operations.
The main disadvantage of fuse saving is that all customers on the circuit
see a momentary interruption for lateral faults. Because of this, many utilities
are switching to a fuse blowing scheme. The instantaneous relay trip is
disabled, and the fuse is always allowed to blow. The fuse blowing scheme
1791_book.fm Page 417 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC