
412 Electric Power Distribution Handbook
8.6.2 Current-Limiting Fuse Coordination
Coordinating two current-limiting fuses is similar to coordinating two expul-
sion links. Plot the time-current characteristics and ensure that the maximum
clearing time of the load-side fuse is less than 75% of the minimum-melting
time of the source-side fuse over the range of fault currents available at the
load-side fuse. The 75% factor accounts for damage to the source-side fuse.
Unlike expulsion links, current-limiting fuses can coordinate to very high
currents. For coordination at higher currents than are shown on published
time-current characteristics (operations faster than 0.01 sec), ensure that the
maximum clearing I
2
t of the load-side fuse is less than 75% of the minimum-
melt I
2
t of the source-side fuse. Manufacturers provide both of these I
2
t values
for current-limiting fuses.
Coordinating an expulsion link with a current-limiting fuse follows similar
principles. Because the melting and clearing characteristics of current-limit-
ing fuses are so much steeper than those of expulsion links, coordination is
sometimes difficult; the operating characteristic curves are more likely to
cross over. A load-side current-limiting fuse coordinates over a wide range
of fault current. For a source-side current-limiting fuse, the clearing-time
limitations of expulsion links (to about 0.8 cycles) prevent coordination at
high currents. For currents above this value, either both will operate, or just
the current-limiting fuse will operate.
Backup current-limiting fuse coordination requires special attention. To
ensure that the CLF does not try to operate for currents below its minimum
interrupting rating, the intersection of the expulsion fuse’s total-clearing
curve and the backup fuse’s minimum-melting curve must be greater than
the maximum interrupting rating of the backup fuse. Normally, we select
backup current-limiting fuses for use with expulsion links based on matched-
melt coordination. Select a backup current-limiting fuse that has a maximum
melting I
2
t below the maximum clear I
2
t of the expulsion element. Also, check
the time-current curves of the devices. The expulsion link should always
clear for fault currents in the low-current operating region, especially below
the minimum interrupting current of the current-limiting fuse.
With matched-melt coordination, the expulsion fuse always operates,
including when the backup current-limiting fuse operates. In overhead
applications with an expulsion fuse in a cutout, the dropout of the expulsion
fuse provides a visible indication when the fuse(s) operate. Also, the backup
fuse is unlikely to have full voltage across it.
The maximum melting I
2
t of expulsion links is not provided from curves
or data. To estimate this, take the minimum melting I
2
t calculated from the
minimum-melt curve at 0.0125 sec, and multiply by 1.2 for tin links or 1.1
for silver links. The multiplier allows for conservatism in minimum-melt
curves and for manufacturing tolerances.
Somewhat less conservatively, experience has shown that fuses coordinate
well if the maximum melt I
2
t of the expulsion link does not exceed twice the
minimum melt I
2
t of the backup fuse (IEEE Std. C37.48-1997). We can tighten
1791_book.fm Page 412 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC