50-62 The Civil Engineering Handbook, Second Edition
Curtain walls are similar to panel walls except that they are not supported at each story by the frame
of the building; rather, they are self supporting. However, they are often anchored to the building frame
at each floor to provide lateral support.
A bearing wall may be defined as one that carries any vertical load in addition to its own weight. Such
walls may be constructed of stone masonry, brick, concrete block, or reinforced concrete. Occasional
projections or pilasters add to the strength of the wall and are often used at points of load concentration.
Bearing walls may be of either single or double thickness, the advantage of the latter type being that the
air space between the walls renders the interior of the building less liable to temperature variation and
makes the wall itself more nearly moistureproof. On account of the greater gross thickness of the double
wall, such construction reduces the available floor space.
According to ACI Code Sec. 14.5.2 the load capacity of a wall is given by
(50.139)
where fP
nw
=design axial load strength
A
g
=gross area of section, in.
2
l
c
=vertical distance between supports, in.
h = thickness of wall, in.
f = 0.7
and where the effective length factor k is taken as 0.8 for walls restrained against rotation at top or bottom
or both, 1.0 for walls unrestrained against rotation at both ends, and 2.0 for walls not braced against
lateral translation.
In the case of concentrated loads, the length of the wall to be considered as effective for each should
not exceed the center-to-center distance between loads; nor should it exceed the width of the bearing
plus 4 times the wall thickness. Reinforced concrete bearing walls should have a thickness of at least
1/25 times the unsupported height or width, whichever is shorter. Reinforced concrete bearing walls of
buildings should be not less than 4 in. thick.
Minimum ratio of horizontal reinforcement area to gross concrete area should be 0.0020 for deformed
bars not larger than #5 — with specified yield strength not less than 60,000 psi or 0.0025 for other
deformed bars — or 0.0025 for welded wire fabric not larger than W31 or D31. Minimum ratio of vertical
thermal area to gross concrete area should be 0.0012 for deformed bars not larger than #5 — with
specified yield strength not less than 60,000 psi or 0.0015 for other deformed bars — or 0.0012 for welded
wire fabric not larger than W31 or D31. In addition to the minimum reinforcement requirement, not
less than two #5 bars shall be provided around all window and door openings. Such bars shall be extended
to develop the bar beyond the corners of the openings but not less than 24 in.
Walls more than 10 in. thick should have reinforcement for each direction placed in two layers parallel
with faces of wall. Vertical and horizontal reinforcement should not be spaced further apart than three
times the wall thickness, or 18 in. Vertical reinforcement need not be enclosed by lateral ties if vertical
reinforcement area is not greater than 0.01 times gross concrete area, or where vertical reinforcement is
not required as compression reinforcement.
Quantity of reinforcement and limits of thickness mentioned above are waived where structural
analysis shows adequate strength and stability. Walls should be anchored to intersecting elements such
as floors, roofs, or to columns, pilasters, buttresses, and intersecting walls, or footings.
Basement Walls
In determining the thickness of basement walls, the lateral pressure of the earth, if any, must be considered
in addition to other structural features. If it is part of a bearing wall, the lower portion may be designed
either as a slab supported by the basement and floors or as a retaining wall, depending upon the type of
ffPfA
kl
h
nw c g
c
=
¢
-
Ê
Ë
Á
ˆ
¯
˜
È
Î
Í
Í
˘
˚
˙
˙
055 1
32
2
.