motors as in start mode the motor may not develop sufficient torque to
allow the pump to accelerate. An approximate limit of 30 kw has been
quoted as a maximum for Start/Delta starting.
Change-over from Star to Delta can cause problems. Timing is very
important and also the method of switching. Open switching completely
breaks the circuit during transition. This break, and the subsequent
switch to Delta mode can produce high transient currents and large
negative torques. These currents may damage windings and the
torques can damage the shaft between motor and pump. A flexible
coupling will alleviate this effect.
Where Star/Delta is unsuitable, transformer starting may well be an
option although more costly. The supply voltage in the initial stage is
reduced to a percentage of mains supply voltage through use of a trans-
former. Typically three tappings are provided on the transformer to
allow for difference between actual and anticipated values. These
tappings may represent voltages in the range 60—80% of mains
voltage. As the motor approaches its maximum speed the supply is
switched onto mains voltage. Complicated switching arrangements
reduce transient currents during switching.
10.6.3 Variable speed or ‘soft’ start
A large number of alternative arrangements of variable speed drives are
available. These allow the engineer to achieve fully automatic control of
pumping in many instances. Synchronous motors, induction motors and
frequency converters all permit a more prolonged start time to be
achieved so that both pump start and normal shutdown surge effects
can be reduced from those that would be attained with a straight-
forward direct start. The pump can be gradually ‘ramped’ up and
down, with the changing speed producing corresponding adjustments
in discharge and delivery head.
10.7 Case studies of pump start
10.7.1 Simulation of direct start in solo pumping
The pump is attempting to deliver into a rising main filled with a static
column of liquid. Not surprisingly the pump will begin by operating
close to its shut-valve condition with the only flow developed being
that which can be accommodated within the pipeline due to compres-
sion of the water and expansion of the pipe cross-section under the
141
Pumps