Where a pumping system operates over a range of delivery pressures,
say high daytime pressure and lower night time pressure, the vessel gas
charge will expand as pressure drops, leaving a reduced water volume in
the vessel. To restore sufficient water volume, some air can be vented
from the vessel to ensure sufficient water is contained for surge pur-
poses. Transient analysis will yield information on the necessary
volumes of air/water over the range of operating pressure conditions.
If a large installation requires several vessels for surge protection
then, provided the vessels are all on one level, they can be treated as
one vessel controlled by a single-level sensing system. A single solenoid
valve controls air flow to all vessels, ensuring that the same pressure is
achieved throughout.
The same compressor/air receiver system may be used to supply air to
vessels serving several mains at the same pumping station. These mains
may operate at different pressures, with each main requiring its own
transient analysis. Each vessel will have its own level sensing system
and solenoid-operated air inlet valve. If a vessel is receiving air through
its valve and a second vessel requires air then the first vessel should
complete filling and its solenoid valve shut before the second vessel
starts to receive air. Ideally, two solenoid valves should be installed in
parallel at each vessel to provide backup in the event of a valve failure.
13.2.3 Other vessel fittings
To allow access for inspection and maintenance, a manway should be
included in the vessel; typically this will be around 500 mm diameter.
A drain valve should be sited at the lowest point on the vessel for
emptying.
A Bourdon pressure gauge can be installed towards the top of the
vessel connected to the gas charge.
A pressure relief valve can be included in the lower part of the vessel
so that if part of the gas charge has been lost and transient pressures
exceed the normal maximum surge level, this valve will open to prevent
further significant excess pressure rise. Some suppliers include a relief
valve on top of the vessel with air being discharged but this allows
the remaining gas charge to be further depleted.
Vessels installed out of doors may require winter protection,
especially if in an exposed location subject to wind chill when tempera-
ture can fall to 258C. Tanks and all exposed connections should be
lagged and trace heated as shown in Fig. 12.19. This also applies to
sight glasses, as freezing can cause failure of the tube. System design
218
Pressure transients in water engineering