
13-10
SECONDARY
12)
t
PRIMARY
c
REFERENCE DATA FOR ENGINEERS
\
n=2
SECONDARY
bl
1-n-
C
T
I
l-
b+
B
[
-
I
(""[
t---b----l
D
Fig.
4.
Methods
of
winding transformers.
(C)
Increase winding width.
(D)
Minimize spacing between windings.
(E)
Use bifilar windings.
Means of minimizing capacitance are:
(A)
Increase dielectric thickness
t.
(B)
Reduce winding width
b
and thus area
A.
(C)
Increase number of layers.
(D)
Avoid large potential differences between wind-
ing sections, as the effect of capacitance is
proportional to applied potential squared.
Note:
Leakage inductance and capacitance require-
ments must be compromised in practice since corrective
measures
are
opposites.
Effective interlayer capacitance of a winding may be
reduced by sectionalizing it as shown in Fig.
4D.
This
can be seen from
C,
=
(4C1/3n1)(1
-
lhl)
where,
C,
=
effective capacitance in picofarads,
nl
=
number of layers,
CI
=
capacitance of one layer to another
A
=
area of winding layer
=
(MLT)b inches2,
t
=
thickness of interlayer insulation in inches,
E
=
dielectric constant
J
3
for paper.
=
0.225
A&
picofarads,
Dielectric Insulation and
Corona
For class
A
(Table 6), a maximum dielectric strength
of
40
volts/mil is considered safe for small thicknesses
of insulation. At high operating voltages, due regard
must be paid to corona that occurs before dielectric
breakdown and will in time deteriorate insulation and
cause dielectric failure. Best practice is to operate
insulation at least
25
percent below the corona starting
voltage. Approximate 60-hertz rms corona voltage
V
is
V
(in volts)
=
(34)
log
(loot)
log
800
where
t
=
total insulation thickness in inches. This may
be used as a guide in determining the thickness of
insulation. With the use of varnishes that require no
solvents, but solidify by polymerization, the bubbles
present in the usual varnishes
are
eliminated, and much
higher operating voltages and, hence, reduction in the
size of high-voltage units may be obtained. Epoxy resins
and some polyesters belong in this group. In the design
of high-voltage transformers, the creepage distance
required between wire and core may necessitate the use
of insulating channels covering the high-voltage coil, or
taping of the latter. For units operating at 10 kilovolts or
higher, oil insulation will greatly reduce creepage and,
hence, the size of the transformer.
Temperature and Humidity
Table 6 lists the standard classes of insulating
materials and their limiting operating temperatures.
Table
7
compares the properties of four high-tempera-
ture wire-insulating coatings.
Open-type constructions generally permit greater
cooling than enclosed types, thus allowing smaller sizes
for the same power ratings. Moderate humidity protec-
tion may be obtained by impregnating and dip-coating
or molding transformers in polyester or epoxy resins;
these units provide good heat dissipation but are not as
good in this respect as completely open transformers.
Protection against the detrimental effects of humidity
is commonly obtained by enclosing transformers in
hermetically sealed metal cases. This is particularly
important if very fine wire, high output voltage, or
direct-current potentials are involved. Heat conductivity
to the case exterior may be improved by the use of
asphalt or thermosetting resins as filling materials. Best
conductivity is obtained with high-melting-point silica-
filled asphalts or resins
of
the polyester or epoxy types.
Coils impregnated with these resins dissipate heat best,
since voids in the heat path may be eliminated.
Immersion in oil is an excellent means of removing
heat from transformers.
An
air space or bellows must be
provided to accommodate expansion of oil when heat-
ed.
FERRORESONANT
TRANSFORMERS
Ferroresonant transformers, also known as constant-
voltage transformers or ferroresonant voltage regula-
tors, make use of an alternating-current phenomenon
involving at least one magnetic component in combina-
tion with a suitable capacitor to provide stabilized
voltage to a load when the source voltage fluctuates.
A