
252 Refrigeration Systems and Applications
remainder is expanded through a throttling valve to the evaporator, thus completing the cycle. As
the working input required to circulate the fluid is typically less than 1% of the heat supplied to
the boiler, the COP may be defined as the ratio of evaporator refrigeration load to heat input to the
boiler as follows:
COP =
˙
Q
L
˙
Q
B
(5.66)
where
˙
Q
L
is evaporator refrigeration load in kW and
˙
Q
B
is heat input to the boiler in kW.
In the past, Aphornratana et al. (2001) have developed a new jet ejector refrigeration system
using R-11 as the refrigerant as shown in Figure 5.28. All vessels in the systems were constructed
from galvanized steel. The boiler was designed to be electrically heated, with two 4 kW electric
heaters being located at the lower end. At its upper end, three baffle plates were welded to the vessel
to prevent liquid droplets being carried over with the refrigerant vapor. The evaporator design was
similar to that of the boiler. A single 3 kW electric heater was used to simulate a cooling load.
A water-cooled plate type heat exchanger was used as a condenser. Cooling water was supplied at
32
◦
C. The boiler was covered with 40 mm thickness of glass wool with aluminum foil backing.
The evaporator was covered with 30 mm thickness of neoprene foam rubber. A diaphragm pump
was used to circulate liquid refrigerant from the receiver tank to the boiler and the evaporator.
The pump was driven by a variable-speed 1/4 hp motor. One drawback of using the diaphragm
pump is cavitation of the liquid refrigerant in the suction line due to pressure drop through an
inlet check valve. Therefore, a small chiller was used to subcool the liquid R-11 before entering
the pump. Figure 5.28c shows a detailed schematic diagram of the experimental ejector. The
nozzle was mounted on a threaded shaft, which allowed the position of the nozzle to be adjusted.
A mixing chamber with throat diameter of 8 mm was used: in the inlet section of the mixing
chamber, the mixing section is a constant are a duct while in the exit section, the mixing section
is a convergent duct.
Aphornratana et al. experiments showed that an ejector refrigeration system using R-11 proved
to be practical and could provide reasonably acceptable performance. It can provide a cooling
temperature as low as −5
◦
C. The cooling capacity ranged from 500 to 1700 W with COP ranging
from 0.1 to 0.25.
5.6 Thermoelectric Refrigeration
This type of system is used to move heat from one area to another by the use of electrical energy. The
electrical energy, rather than the refrigerant, serves as a “carrier.” The essential use of thermoelectric
systems has been in portable refrigerators, water coolers, cooling of scientific apparatus used in
space exploration, and in aircraft. The main advantage of this system is that there are no moving
parts. Therefore, the system is compact, quiet, and needs little service.
Thermoelectric coolers are solid state equipment used in applications where temperature sta-
bilization, temperature cycling, or cooling below ambient temperature are required. There are
many products using thermoelectric coolers, including charge-coupled device (CCD) cameras, laser
diodes, microprocessors, blood analyzers, and portable picnic coolers.
Thermoelectrics are based on the Peltier Effect, discovered in 1834, by which DC current applied
across two dissimilar materials causes a temperature differential. The Peltier effect is one of the three
thermoelectric effects, the other two being known as the Seebeck effect and Thomson effect . Whereas
the last two effects act on a single conductor, the Peltier effect is a typical junction phenomenon.
The three effects are connected to each other by a simple relationship (Godfrey, 1996).
The typical thermoelectric module is manufactured using two thin ceramic wafers with a series of
P- and N-doped bismuth telluride semiconductor materials sandwiched between them. The ceramic
material on both sides of the thermoelectric adds rigidity and the necessary electrical insulation.