
The cost and sophistication of oil-preaslue
governors
detract from their ‘appropriateness in rural areas. They
should be considered only where streamflow is relatively
small and provisions
for
the storage of water not used
immediately for power generation are made.
In Nepal, where water resources are sometimes limited
and a governor was required to make more efficient use
of the available water, Balaju Yantra Shala, with Swiss
assistance, developed an alternative governor design
which, unlike conventional designs, could be fabricated
largely in-country. To keep the device simple, a propor-
tional-type governor, where the position of the tubine
valve is determined by turbine speed, was designed. It
uses water under forebay pressure, rather than oil under
pressure generated by a separate pump, as the working
fluid. Because of the lower workirg pressure, the sor-
vocylinder that activates the turbine valve has to be
relatively larger in size. As with conventional govern-
ors, a flyball assembly senses turbine speed. As the
speed changes with changes in load, a pilot valve con-
nected to the flyball assembly controls the portion of
the forebay prossure that actually acts on the servocy-
linder, which in turn opens and closes the turbine valve
to compensate for the changes in load.
For the 30 kW plant at Dhading, Nepal, the speed devia-
tion from its nominal value varies from +lO% under no-
load conditions to -6% at rated load to -20% under full
load. However, it remains within a range of f4% for the
output range from about lo-25 kW and is therefore ade-
huate under normal loads. Because of voltage regula-
tion
of
the generator output, voltage remains constant
over ths entire range of loads. The Swiss Center for
Appropriate technology (SKAT) is preparing Design
Manual for a Simple Mechanical Governor and has
already prepared, a summary reportmA brief descrip-
tion of the Eovernor and its oueration can also be found
1
in Local Experience with Micro-Hydro Technology (78).
Details of the operation of the govemor installed at
Dhading can be found in the report, The Dhadinp Micro-
Hydropower Plant i77!. This publication also discusses
the procedure for tuning the governor, which is critical
to avoid erratic operation.
Mechanical governor
For micro-hydropower plants, turbines can be fairly
small, and reduced forces are required to manipulate
turbines valves. In these cases, mechanical governors
have sometimes been used. Typically, these incorporate
a flyball arrangement driven by the turbine shaft. The
output from this assembly is used directly to drive a
valve on the turbine rather than to drive small interme-
diary valves controlling the flow of oil. The flyballs
associated with a mechanical governor are much more
massive, because a significantly larger force is required
to drive the valve controlling waterflow to the turbine
than to drive a pilot va!ve of ax1 oil-pressure governor.
Load controller
The load controller is an electronic device that main-
tains a constant electrical load on a generator in spite
of changing user loads, thereby permitting the use of a
turbine with no flow-regulating devices. It replaces the
governor that adjusts the flow through a turbine to keep
up with the fluctuating electrical or mechanical loads
and that requires speed-sensing devices, actuating
mechanisms, and valves, gates,
or
adjustable blades,
depending on the type of turbine used.
The flow through the turbine is set at some value and a
constant quantity of electrical
power
is generated.
Assume that the consumer initially uses all this power.
Because the waterpower into the plants i:i matched to
the electrical load, the generator operates as it should
and generates power at the required frequency of, for
example, 50 Hz. If the consumer switches off some
appliances ot other loads that have been in use, the
electrical power used becomes less than the waterpower
available to the plant, and the turbine and generator
speed, and frequency generated, begin to increase. This
change is sensed electronically by the load controller,
which then adds a ballast load
of
sufficient size at the
generator output to dissipate power equivalent to that
which was switched off. Therefore, in spite of a change
in consumer load, the total load on the generator
remains constant.
When a turbine is used to drive mechanical equipment in
addition to a generator, a load controller can maintain
the system speed and frequency at its design value
regardless of fluctuating mechanical and electrical
loads. In “Energy for Rural Development” (591, Holland
describes a sawmill where a 25 hp turbine mechanically
drives the principal load, a saw and cable drum drive for
a carriage to carry the logs, and, in addition, is perma-
nently coupled to an ac generator that provides power
for cooking with storage cookers (see Heat storage
cookeq p. 242) and for lighting. As soon as the saw
starts to operate, a load controller automatically shifts
power from the ballast load to the saw so that as much
power as necessary is available for cutting.
If a load controller is located within the powerhouse, a
controller that senses current, voltage, or shaft speed
can be used. However, it might prove more advanta-
geous to locate the controller away from the power-
house to use the excess power more effectively. In this
case, only frequency or voltage can be used to deter-
mine the state of the system. Use of voltage may be
unsatisfactory because it is affected by factors other
than the total load imposed on the system: voltage
losses in the distribution line, power factor, and the
action of the voltage regulator incorporated in the
generator. Determining the state of the system by
sensing frequency is therefore the most widely used
approach.
The principal advantage of a load controller is that the
overail system becomes simpler and less costly. It not
only eliminates the need for an intricate governor and
actuating mechanism, but it allows the design of the
turbine to be simplified. A less sophisticated system
increases the chances for long-term viability and
reduces equipment cost considerably for plants in the
micro-hydropower range. For example, rather than a
cost of $lO,O!lO for an oil-pressure governor for an 8 kW
204 Governing