the resulting load. At this load, there was a catastrophic failure (buck-
ling) of the pipe (see Figs. 6.25 and 6.26).
30-in-diameter live load test. This test was also conducted with only
1 ft of cover over the pipe to simulate a minimum cover application.
The load was first applied to the surface of the soil but directly to the
side of the pipe. Again, because of the catastrophic failure of the 18-in
pipe, the 16,000 lb was distributed over a 10-in 40-in area—twice
the area of the 18-in test. The loading plate penetrated the soil about
1 in. The pipe showed no adverse reaction.
The loading plate was then positioned on the soil surface just off the
centerline of the pipe (the most critical position for a live load), so
the load is over one-half of the pipe. The load was increased toward
the required 16,000 lb. At 16,000 lb, the plate penetrated the soil
about 4 in and otherwise was in equilibrium (see Fig. 6.27). The load
was held for several minutes, and there was no adverse reaction of the
pipe (see Fig. 6.28). This pipe, when properly installed with cover
heights of 1 ft or greater, will withstand an H-20 loading.
The load was gradually increased to determine what load would
cause failure. At 18,853 lb, a soil failure wedge formed, the plate began
to penetrate the soil, and the pipe could not support the resulting load.
At this load, there was a catastrophic failure (buckling) of the pipe (see
Figs. 6.29 and 6.30).
314 Chapter Six
Figure 6.25 Photograph showing soil surface, plate penetration, and resulting soil rise
due to buckling of the pipe.