
POWER QUALITY 97
In terms of rms values,
I
n
= 3I
3
(2.102)
That is, the rms current in the neutral line is three times the rms current in each
line’s third harmonic. There is considerable likelihood, therefore, that harmonic-
generating loads will cause the neutral to carry even more current than the phase
conductors, not less!
The same argument about harmonics adding in the neutral applies to all of
the harmonic numbers that are multiples of 3 (since 3 × n × 120
◦
= n360
◦
= 0
◦
).
That is, the third, sixth, ninth, twelfth, ...harmonics all add to the neutral current
in an amount equal to three times their phase-current harmonics. Notice, by the
way, that harmonics not divisible by 3 cancel out in the same way that the
fundamental cancels—for example, the second harmonic:
i
n−2nd harmonic
=
√
2I
2
{cos(2ωt) + cos[2(ωt + 120
◦
)] + cos[2(ωt − 120
◦
)]}
(2.103)
The terms in the bracket are
cos(2ωt) + cos(2ωt + 240
◦
) + cos(2ωt − 240
◦
) = cos 2ωt + cos(2ωt − 120
◦
)
+ cos(2ωt + 120
◦
) = 0
so the second harmonic currents cancel just as the fundamental did. This will be
the case for all harmonics not divisible by 3.
For currents that show half-wave symmetry, there are no even harmonics, so
the only harmonics that appear on the neutral line for balanced loads of this sort
will be third, 9th, 15th, 21st, ... etc. These odd harmonics, divisible by three,
are called triplen harmonics.
Example 2.13 Neutral-Line Current. A four-wire, wye-connected balanced
load has phase currents described by the following harmonics:
Harmonic rms Current (A)
1 100
350
520
710
98
11 4
13 2
Find the rms current flowing in the neutral wire and compare it to the rms
phase current.